Flexible medium voltage cable (N)TSCGECEWOEU MT BM PLUS

(N)TSCGECEWOEU MT BM PLUS
flame retardant acc. IEC 60332-1-2 cable to a large extent oil resistant max. permitted temperature at conductor 90 °C cable for reeling application installation in free air without UV-protection (cable UV-resistant)

flame retardant acc. IEC 60332-1-2 flame retardant acc. IEC 60332-1-2

cable to a large extent oil resistant cable to a large extent oil resistant

max. permitted temperature at conductor 90 °C max. permitted temperature at conductor 90 °C

cable for reeling application cable for reeling application

installation in free air without UV-protection (cable UV-resistant) installation in free air without UV-protection (cable UV-resistant)

  • Technical data
  • Item list
  • Application
  • Technical documents
StandardVDE 0250-813
Conductor materialtinned copper
Conductor classclass 5 = fine stranded
Insulationrubber 3GI3
Electrical field controlinner and outer semiconducting rubber layer
Central fillersemiconductive compound on polyester support
Material inner sheathrubber (CR) 5GM5
Torsion+/- 25 °/m
Flame-retardantVDE 0482-332-1-2/IEC 60332-1-2
UV-resistantyes
Oil-resistantEN 60811-2-1
Ozone-resistantyes
Maximum permitted conductor temperature90 °C
Permitted outer cable temperature, fixed-40 - +80 °C
Permitted outer cable temperature, in motion/during installation-25 - +80 °C
Bending radius, fixed installation6 x DA
Bending radius, moving application15 x DA

Flexible cable suitable for reeling drum of tunnel boring machines and generally for tunnel application. Other applications have to be agreed with Faber Kabel, otherwise warranty may get lost.

Item numberItem nameAl
kg/km
Cu
kg/km
Weight
kg/km
051713 (N)TSCGECEWOEU MT BM PLUS 03X50 + 03X25/3E + 03X2,5+UEL KON 12/20 kV RT 1896.0 5190.0

All images shown here are for illustrations and product reference purposes only.

Who we are.

Faber has numbered amongst the top providers in the cable and wire industry for over 68 years. We convince our customers with high-performing products and tested quality.

We are appreciated for our know-how, our service-orientation and our absolute adherence to delivery dates. Because we find: Nothing is more important than being a strong and dependable partner.

Contact.

Klaus Faber AG
Lebacher Straße 152 – 156
66113 Saarbrücken
Germany

Phone +49 681 97 11-0
Fax +49 681 97 11-289

Newsletter.