Including 1% procurement surcharge. No responsibility for the information!
+++ 17.11.2017 + AL 218.63 + CU 588.20 +++ 16.11.2017 + AL 215.27 + CU 580.37 +++ 15.11.2017 + AL 217.13 + CU 594.03 +++ 14.11.2017 + AL 220.03 + CU 593.90 +++ 13.11.2017 + AL 219.28 + CU 596.70
Your language: DE | EN
Discover the diversity of Faber Kabel.

Discover the diversity of Faber Kabel.

More cable is impossible.

Medium voltage cable N2XS(FL)2Y

N2XS(FL)2Y
cable suitable for direct burial max. permitted temperature at conductor 90 °C min. installation temperature -20 °C installation in free air without UV-protection (cable UV-resistant) cable for use in water cable with VDE-certification

cable suitable for direct burial cable suitable for direct burial

max. permitted temperature at conductor 90 °C max. permitted temperature at conductor 90 °C

min. installation temperature -20 °C min. installation temperature -20 °C

installation in free air without UV-protection (cable UV-resistant) installation in free air without UV-protection (cable UV-resistant)

cable for use in water cable for use in water

cable with VDE-certification cable with VDE-certification

  • Technical data
  • Item list
  • Application
  • Technical documents
StandardVDE 0276-620
Direct burialyes
VDEyes
Conductor materialbare copper
Conductor classclass 2 = stranded
InsulationXLPE DIX8
Sheathing materialpolyethylene DMP2
Bonded sheathyes
Transversely watertightyes
Longitudinally watertightyes
Colour outer sheathblack
UV-resistantyes
Maximum permitted conductor temperature90 °C
Permitted outer cable temperature, fixed70 °C
Permitted outer cable temperature, in motion/during installation-20 - +70 °C
Bending radius, fixed installation15 x DA

For installation in the ground, in water, outdoors, indoors and in cable ducts for power stations, industrial applications and distribution networks. The high mechanical durability of the PE-sheath permits strong mechanical stress during installation or operation. This cable is also suitable for unfavourable operating conditions, specifically where there is a need to avoid water penetration both crosswise and lengthwise following mechanical damage.

Item numberItem nameAl
kg/km
Cu
kg/km
Weight
kg/km
013784 N2XS(FL)2Y 01X35/16 6/10 kV SW 518.0 861.0
014065 N2XS(FL)2Y 01X50/16 6/10 kV SW 662.0 1150.0
013521 N2XS(FL)2Y 01X70/16 6/10 kV SW 854.0 1300.0
012467 N2XS(FL)2Y 01X95/16 6/10 kV SW 1094.0 1450.0
012459 N2XS(FL)2Y 01X120/16 6/10 kV SW 1334.0 1900.0
012639 N2XS(FL)2Y 01X150/25 6/10 kV SW 1723.0 1997.0
012582 N2XS(FL)2Y 01X185/25 6/10 kV SW 2059.0 2463.0
011825 N2XS(FL)2Y 01X240/25 6/10 kV SW 2587.0 3050.0
012001 N2XS(FL)2Y 01X300/25 6/10 kV SW 3163.0 3720.0
014137 N2XS(FL)2Y 01X400/35 6/10 kV SW 4234.0 4500.0
012613 N2XS(FL)2Y 01X500/35 6/10 kV SW 5194.0 5878.0
012654 N2XS(FL)2Y 01X630/35 6/10 kV SW 6442.0 7014.0
013641 N2XS(FL)2Y 01X35/16 12/20 kV SW 518.0 1050.0
013117 N2XS(FL)2Y 01X50/16 12/20 kV SW 662.0 1170.0
013118 N2XS(FL)2Y 01X70/16 12/20 kV SW 854.0 1470.0
011786 N2XS(FL)2Y 01X95/16 12/20 kV SW 1094.0 1900.0
013119 N2XS(FL)2Y 01X120/16 12/20 kV SW 1334.0 2260.0
013033 N2XS(FL)2Y 01X150/25 12/20 kV SW 1723.0 2318.0
014210 N2XS(FL)2Y 01X185/25 12/20 kV SW 2059.0 3045.0
013030 N2XS(FL)2Y 01X240/25 12/20 kV SW 2587.0 3700.0
013663 N2XS(FL)2Y 01X95 RM/16 18/30 kV SW 1094.0 1900.0
013640 N2XS(FL)2Y 01X150/25 18/30 kV SW 1723.0 2650.0
013664 N2XS(FL)2Y 01X240 RM/25 18/30 kV SW 2587.0 3500.0
012779 N2XS(FL)2Y 01X300/25 18/30 kV SW 3163.0 4151.0
013227 N2XS(FL)2Y 01X400/35 18/30 kV SW 4234.0 5045.0
011750 N2XS(FL)2Y 01X300/25 12/20 kV SW 3163.0 3940.0
013561 N2XS(FL)2Y 01X400/35 12/20 kV SW 4234.0 4850.0
012228 N2XS(FL)2Y 01X500/35 12/20 kV SW 5194.0 5948.0
013974 N2XS(FL)2Y 01X630/35 12/20 kV SW 6442.0 7400.0

All images shown here are for illustrations and product reference purposes only.

Who we are.

Faber Kabel has numbered amongst the top providers in the cable and wire industry for over 47 years. We convince our customers with high-performing products and tested quality.

We are appreciated for our know-how, our service-orientation and our absolute adherence to delivery dates. Because we find: Nothing is more important than being a strong and dependable partner.

Contact.

Klaus Faber AG
Lebacher Straße 152 – 156
66113 Saarbrücken
Germany

Phone +49 681 97 11-0
Fax +49 681 97 11-289

Newsletter.