Including 1% procurement surcharge. No responsibility for the information!
+++ 23.11.2017 + AL 217.19 + CU 598.52 +++ 22.11.2017 + AL 215.65 + CU 595.88 +++ 21.11.2017 + AL 215.01 + CU 586.20 +++ 20.11.2017 + AL 215.61 + CU 583.62 +++ 17.11.2017 + AL 218.63 + CU 588.20
Your language: DE | EN
Discover the diversity of Faber Kabel.

Discover the diversity of Faber Kabel.

More cable is impossible.

Communication cable with circuit integrity JE-H(St)H FE180/E30-E90

JE-H(St)H FE180/E30-E90
cable with circuit integrity 30 - 90 min cable with function maintainance 180 min flame retardant acc. IEC 60332-3-24 cable with low smoke IEC 61034 cable halogen-free cable with VDE-certification cable conform to Low Voltage directive

cable with circuit integrity 30 - 90 min cable with circuit integrity 30 - 90 min

cable with function maintainance 180 min cable with function maintainance 180 min

flame retardant acc. IEC 60332-3-24 flame retardant acc. IEC 60332-3-24

cable with low smoke IEC 61034 cable with low smoke IEC 61034

cable halogen-free cable halogen-free

cable with VDE-certification cable with VDE-certification

cable conform to Low Voltage directive cable conform to Low Voltage directive

  • Technical data
  • Item list
  • Application
  • Technical documents
StandardVDE 0815
VDEyes
Conductor materialbare copper
Conductor classclass 1 = solid
InsulationFRNC-compound HI1
Sheathing materialFRNC-compound HM2
Flame-retardantVDE 0482-266-2-4/IEC 60332-3-24 (Kat. C)
Smoke densityDIN EN 61034/IEC 61034
Halogen-freeDIN EN 50267/IEC 60754
Fire-resistantFE 180
Circuit integrityE30-E90
Permitted outer cable temperature, fixed-5 - +50 °C
Bending radius, fixed installation7.5 x DA

For signal transmission within systems for measuring-, control-, data- and regulation technology and for use as an installation cablefire hazard rooms with a high concentration of people and material assets and for installation of fire survival cable systems according to DIN 4102 part 12. For fixed installation in dry and wet rooms.

Item numberItem nameAl
kg/km
Cu
kg/km
Weight
kg/km
101620 JE-H(St)H...BD...E30-E90 01X2X0,8 OR 12.0 57.0
100275 JE-H(St)H...BD...E30-E90 02X2X0,8 OR 25.0 76.0
100276 JE-H(St)H...BD...E30-E90 04X2X0,8 OR 45.0 130.0
100277 JE-H(St)H...BD...E30-E90 08X2X0,8 OR 85.0 232.0
100292 JE-H(St)H...BD...E30-E90 12X2X0,8 OR 126.0 318.0
100278 JE-H(St)H...BD...E30-E90 16X2X0,8 OR 166.0 430.0
100279 JE-H(St)H...BD...E30-E90 20X2X0,8 OR 206.0 514.0
100280 JE-H(St)H...BD...E30-E90 32X2X0,8 OR 326.0 730.0
100281 JE-H(St)H...BD...E30-E90 40X2X0,8 OR 407.0 962.0
100282 JE-H(St)H...BD...E30-E90 52X2X0,8 OR 529.0 1200.0

All images shown here are for illustrations and product reference purposes only.

Who we are.

Faber Kabel has numbered amongst the top providers in the cable and wire industry for over 47 years. We convince our customers with high-performing products and tested quality.

We are appreciated for our know-how, our service-orientation and our absolute adherence to delivery dates. Because we find: Nothing is more important than being a strong and dependable partner.

Contact.

Klaus Faber AG
Lebacher Straße 152 – 156
66113 Saarbrücken
Germany

Phone +49 681 97 11-0
Fax +49 681 97 11-289

Newsletter.