Power cable (N)2XY-J FR 05X120 0,6/1 kV SW IEC 60502

Item number 012419

(N)2XY-J FR 05X120 0,6/1 kV SW IEC 60502
flame retardant acc. IEC 60332-3-24 cable suitable for direct burial max. permitted temperature at conductor 90 °C min. installation temperature -5 °C installation in free air without UV-protection (cable UV-resistant) cable conform to Low Voltage directive

flame retardant acc. IEC 60332-3-24 flame retardant acc. IEC 60332-3-24

cable suitable for direct burial cable suitable for direct burial

max. permitted temperature at conductor 90 °C max. permitted temperature at conductor 90 °C

min. installation temperature -5 °C min. installation temperature -5 °C

installation in free air without UV-protection (cable UV-resistant) installation in free air without UV-protection (cable UV-resistant)

cable conform to Low Voltage directive cable conform to Low Voltage directive

  • Datasheet
  • Application
  • Technical documents
StandardIEC 60502
Conductor materialbare copper
Conductor classclass 1, from 25 sqmm class 2
InsulationXLPE DIX3
Sheathing materialPVC ST2, UV-resistant
Colour outer sheathblack
Flame-retardantVDE 0482-266-2-4/IEC 60332-3-24 (Cat. C)
Flame-retardantVDE 0482-266-2-4/IEC 60332-3-24 (Kat. C)
For outdoor useyes
Maximum permitted conductor temperature90 °C
Permitted outer cable temperature, fixed-35 - +70 °C
Permitted outer cable temperature, in motion/during installation-5 - +70 °C
Bending radius, fixed installation15 x DA
Nominal voltage Uo600 V
Nominal voltage U1000 V
Maximum permitted operating voltage in three-phase systems1.2 kV
Test voltage4 kV
Core identificationcolours acc. to VDE 0293 (HD 308); more than 5 cores: gn-ye + numbers
Conductor shape (Faber)RMv
Number of cores5
Nominal cross section120 mm²
Conductor resistance0.153 Ohm/km
Insulation wall thickness1.2 mm
Ampacity in air (30 °C)359 A
Ampacity in ground (20 °C)349 A
Outer diameter approx.50.9 mm
colourblack

For fixed installation in buildings, outdoors, in the ground and in water.

All images shown here are for illustrations and product reference purposes only.

Who we are.

Faber has numbered amongst the top providers in the cable and wire industry for over 47 years. We convince our customers with high-performing products and tested quality.

We are appreciated for our know-how, our service-orientation and our absolute adherence to delivery dates. Because we find: Nothing is more important than being a strong and dependable partner.

Contact.

Klaus Faber AG
Lebacher Straße 152 – 156
66113 Saarbrücken
Germany

Phone +49 681 97 11-0
Fax +49 681 97 11-289

Newsletter.