FRNC power cable N2XH-J 04X50/25 SW

Item number 013240

N2XH-J 04X50/25 SW
flame retardant acc. IEC 60332-3-24 cable with low smoke IEC 61034 cable halogen-free max. permitted temperature at conductor 90 °C installation in free air only with UV-protection (cable not UV-resistant) cable with VDE-certification cable conform to Low Voltage directive

flame retardant acc. IEC 60332-3-24 flame retardant acc. IEC 60332-3-24

cable with low smoke IEC 61034 cable with low smoke IEC 61034

cable halogen-free cable halogen-free

max. permitted temperature at conductor 90 °C max. permitted temperature at conductor 90 °C

installation in free air only with UV-protection (cable not UV-resistant) installation in free air only with UV-protection (cable not UV-resistant)

cable with VDE-certification cable with VDE-certification

cable conform to Low Voltage directive cable conform to Low Voltage directive

  • Datasheet
  • Application
  • Technical documents
StandardVDE 0276-604
Conductor materialbare copper
Conductor classclass 1, from 25 sqmm class 2
InsulationXLPE 2XI1
Sheathing materialFRNC-compound HM4
Flame-retardantDIN EN 50266-2-4/VDE 0482-266-2-4/IEC 60332-3-24 (cat. C)
Smoke densityDIN EN 61034/IEC 61034
Halogen-freeDIN EN 50267/IEC 60754
Maximum permitted conductor temperature90 °C
Permitted outer cable temperature, fixed-30 - +70 °C
Permitted outer cable temperature, in motion/during installation-5 - +70 °C
Bending radius, fixed installation15 x DA
Nominal voltage Uo600 V
Protective conductoryes
Nominal voltage U1000 V
Maximum permitted operating voltage in three-phase systems1.2 kV
Test voltage4 kV
Core identificationcolours acc. to VDE 0293 (HD 308); more than 5 cores: gn-ye + numbers
Conductor shapesector-shaped
Conductor shape (Faber)SMv
Number of cores5
Nominal cross section50 mm²
Conductor resistance0.387 Ohm/km
Insulation wall thickness1 mm
Ampacity in air (30 °C)197 A
Short-circuit current (1 s)7.15 kA
Bending radius, fixed installation370 mm
Outer diameter approx.30.8 mm
Colour of outer sheathblack
Tensile strength (during installation)11250 N
colourblack

Zero-halogen, low-smoke power cable with improved flame-retardance. For fixed installation indoors, in air as well as in concrete, but not for direct burial in the ground or application in water.

All images shown here are for illustrations and product reference purposes only.

Who we are.

Faber Kabel has numbered amongst the top providers in the cable and wire industry for over 47 years. We convince our customers with high-performing products and tested quality.

We are appreciated for our know-how, our service-orientation and our absolute adherence to delivery dates. Because we find: Nothing is more important than being a strong and dependable partner.

Contact.

Klaus Faber AG
Lebacher Straße 152 – 156
66113 Saarbrücken
Germany

Phone +49 681 97 11-0
Fax +49 681 97 11-289

Newsletter.