Item number 020307
flame retardant acc. IEC 60332-1-2
max. permitted temperature at conductor 70 °C
min. installation temperature +5 °C
cable with VDE-certification
cable conform to Low Voltage directive
Standard | VDE 0250-204 |
Conductor material | copper, bare |
Conductor class | class 1, up from 16 sqmm class 2 |
Insulation | PVC TI1 |
Sheathing material | PVC YM1 |
Colour outer sheath | grey RAL 7035 |
Flame-retardant | VDE 0482-332-1-2/IEC 60332-1-2 |
Permitted outer cable temperature, fixed | -40 - +70 °C |
Permitted outer cable temperature, in motion/during installation | 5 - 70 °C |
Nominal voltage Uo | 300 V |
Protective conductor | yes |
Nominal voltage U | 500 V |
Test voltage | 2 kV |
Core identification | colours acc. to VDE 0293 (HD 308); more than 5 cores: gn-ye + numbers |
Conductor shape | round |
Conductor shape (Faber) | RE |
Number of cores | 16 |
Nominal cross section | 1.5 mm² |
Conductor resistance | 12.1 Ohm/km |
Insulation wall thickness | 0.6 mm |
Ampacity in air (30 °C) | 17.5 A |
Wall thickness of sheath | 1.6 mm |
Bending radius, fixed installation | 63.2 mm |
Conductor class | class 1 = solid |
Outer diameter approx. | 15.8 mm |
Cable shape | round |
colour | grey |
For installation in, on or under plaster, in dry, damp or wet rooms as well as in walls and concrete (except for shaken, jolted, tamped concrete). Also suitable for installation outdoors if protected from sunlight.
All images shown here are for illustrations and product reference purposes only.