Item number 080099
flame retardant acc. IEC 60332-1-2
cable suitable for direct burial
max. permitted temperature at conductor 70 °C
min. installation temperature -5 °C
installation in free air without UV-protection (cable UV-resistant)
cable for use in water
cable with VDE-certification
cable with EAC-approval
cable conform to Low Voltage directive
Standard | VDE 0276-603 |
Conductor material | copper, bare |
Conductor class | class 1, from 25 sqmm class 2 |
Insulation | PVC DIV 4 |
Concentric conductor | Cu |
Sheathing material | PVC DMV5 |
Colour outer sheath | black |
Flame-retardant | VDE 0482-332-1-2/IEC 60332-1-2 |
UV-resistant | yes |
For outdoor use | yes |
Maximum permitted conductor temperature | 70 °C |
Permitted outer cable temperature, fixed | 70 °C |
Permitted outer cable temperature, in motion/during installation | -5 - +70 °C |
Nominal voltage Uo | 600 V |
Nominal voltage U | 1000 V |
Maximum permitted operating voltage in three-phase systems | 1.2 kV |
Test voltage | 4 kV |
Core identification | colours acc. to VDE 0293 (HD308) |
Conductor shape | round |
Conductor shape (Faber) | RM |
Number of cores | 4 |
Nominal cross section | 16 mm² |
Conductor resistance | 1.15 Ohm/km |
Insulation wall thickness | 1 mm |
Ampacity in air (30 °C) | 80 A |
Ampacity in ground (20 °C) | 102 A |
Short-circuit current (1 s) | 1.84 kA |
Specific inductivity | 0.285 mH/km |
Wall thickness of sheath | 1.8 mm |
Bending radius, fixed installation | 280.8 mm |
Conductor class | class 2 = stranded |
Outer diameter approx. | 23.4 mm |
Colour of outer sheath | black |
Tensile strength (during installation) | 3200 N |
Cable shape | round |
colour | black |
For fixed installation indoors, outdoors, in the ground, in water and in conrete.