Including 1% procurement surcharge. No responsibility for the information!
+++ 15.12.2017 + AL 210.44 + CU 581.30 +++ 14.12.2017 + AL 210.34 + CU 582.61 +++ 13.12.2017 + AL 210.31 + CU 574.74 +++ 12.12.2017 + AL 208.91 + CU 568.06 +++ 11.12.2017 + AL 209.92 + CU 570.02
Your language: DE | EN
Discover the diversity of Faber.

Discover the diversity of Faber.

More cable is impossible.

Medium voltage cable N2XSY 01X35/16 12/20 kV RT

Item number 011295

N2XSY 01X35/16 12/20 kV RT
flame retardant acc. IEC 60332-1-2 cable suitable for direct burial max. permitted temperature at conductor 90 °C min. installation temperature -5 °C installation in free air only with UV-protection (cable not UV-resistant) cable with VDE-certification

flame retardant acc. IEC 60332-1-2 flame retardant acc. IEC 60332-1-2

cable suitable for direct burial cable suitable for direct burial

max. permitted temperature at conductor 90 °C max. permitted temperature at conductor 90 °C

min. installation temperature -5 °C min. installation temperature -5 °C

installation in free air only with UV-protection (cable not UV-resistant) installation in free air only with UV-protection (cable not UV-resistant)

cable with VDE-certification cable with VDE-certification

  • Datasheet
  • Application
  • Technical documents
StandardVDE 0276-620
Conductor materialbare copper
Conductor classclass 2 = stranded
InsulationXLPE DIX8
Sheathing materialPVC DMV6
Colour outer sheathred
Flame-retardantVDE 0482-332-1-2/IEC 60332-1-2
For outdoor useyes
Maximum permitted conductor temperature90 °C
Permitted outer cable temperature, fixed70 °C
Permitted outer cable temperature, in motion/during installation-5 - +70 °C
Bending radius, fixed installation15 x DA
Nominal voltage Uo12000 V
Nominal voltage U20000 V
Maximum permitted operating voltage in three-phase systems24 kV
Test voltage42 kV
Conductor shaperound
Conductor shape (Faber)RM
Number of cores1
Conductor diameter7.5 mm
Nominal cross section35 mm²
Conductor resistance0.524 Ohm/km
Insulation wall thickness5.5 mm
Ampacity in air (30 °C)200 A
Ampacity in ground (20 °C)189 A
Short-circuit current (1 s)5 kA
Wall thickness of sheath2.5 mm
Bending radius, fixed installation420 mm
Outer diameter approx.28 mm
Colour of outer sheathred
Tensile strength (during installation)1750 N
colourred

For installation in the ground, in water, outdoors, indoors and in cable ducts for power stations, industrial applications and distribution networks. The good installation properties of this cable make installation easy, even on difficult routes. According to VDE 0276-603 cables must be protected from sunlight.

All images shown here are for illustrations and product reference purposes only.

Who we are.

Faber has numbered amongst the top providers in the cable and wire industry for over 47 years. We convince our customers with high-performing products and tested quality.

We are appreciated for our know-how, our service-orientation and our absolute adherence to delivery dates. Because we find: Nothing is more important than being a strong and dependable partner.

Contact.

Klaus Faber AG
Lebacher Straße 152 – 156
66113 Saarbrücken
Germany

Phone +49 681 97 11-0
Fax +49 681 97 11-289

Newsletter.