Including 1% procurement surcharge. No responsibility for the information!
+++ 21.11.2017 + AL 215.01 + CU 586.20 +++ 20.11.2017 + AL 215.61 + CU 583.62 +++ 17.11.2017 + AL 218.63 + CU 588.20 +++ 16.11.2017 + AL 215.27 + CU 580.37 +++ 15.11.2017 + AL 217.13 + CU 594.03
Your language: DE | EN
Discover the diversity of Faber Kabel.

Discover the diversity of Faber Kabel.

More cable is impossible.

Medium voltage cable NA2XS(F)2Y 01X240/25 18/30 kV SW

Item number 011539

NA2XS(F)2Y 01X240/25 18/30 kV SW
cable suitable for direct burial max. permitted temperature at conductor 90 °C min. installation temperature -20 °C installation in free air without UV-protection (cable UV-resistant) cable for use in water cable with VDE-certification

cable suitable for direct burial cable suitable for direct burial

max. permitted temperature at conductor 90 °C max. permitted temperature at conductor 90 °C

min. installation temperature -20 °C min. installation temperature -20 °C

installation in free air without UV-protection (cable UV-resistant) installation in free air without UV-protection (cable UV-resistant)

cable for use in water cable for use in water

cable with VDE-certification cable with VDE-certification

  • Datasheet
  • Application
  • Technical documents
StandardVDE 0276-620
Conductor materialaluminium
Conductor classclass 2 = stranded
InsulationXLPE DIX8
Sheathing materialpolyethylene DMP2
Colour outer sheathblack
Flame-retardantno
UV-resistantyes
Maximum permitted conductor temperature90 °C
Permitted outer cable temperature, fixed70 °C
Permitted outer cable temperature, in motion/during installation-20 - +70 °C
Bending radius, fixed installation15 x DA
Nominal voltage Uo18000 V
Nominal voltage U30000 V
Maximum permitted operating voltage in three-phase systems36 kV
Test voltage63 kV
Conductor shape (Faber)RMv
Number of cores1
Conductor diameter19.2 mm
Nominal cross section240 mm²
Conductor resistance0.125 Ohm/km
Insulation wall thickness8 mm
Ampacity in air (30 °C)496 A
Ampacity in ground (20 °C)422 A
Short-circuit current (1 s)22.6 kA
Wall thickness of sheath2.5 mm
Bending radius, fixed installation660 mm
Outer diameter approx.44 mm
Colour of outer sheathblack
Tensile strength (during installation)7200 N
colourblack

For installation in the ground, in water, outdoors, indoors and in cable ducts for power stations, industrial applications and distribution networks. The high mechanical durability of the PE-sheath permits strong mechanical stress during installation or operation. This cable is also suitable for unfavourable operating conditions, specifically where there is a need to avoid water penetration lengthwise following mechanical damage.

All images shown here are for illustrations and product reference purposes only.

Who we are.

Faber Kabel has numbered amongst the top providers in the cable and wire industry for over 47 years. We convince our customers with high-performing products and tested quality.

We are appreciated for our know-how, our service-orientation and our absolute adherence to delivery dates. Because we find: Nothing is more important than being a strong and dependable partner.

Contact.

Klaus Faber AG
Lebacher Straße 152 – 156
66113 Saarbrücken
Germany

Phone +49 681 97 11-0
Fax +49 681 97 11-289

Newsletter.