Including 1% procurement surcharge. No responsibility for the information!
+++ 24.11.2017 + AL 215.81 + CU 595.34 +++ 23.11.2017 + AL 217.19 + CU 598.52 +++ 22.11.2017 + AL 215.65 + CU 595.88 +++ 21.11.2017 + AL 215.01 + CU 586.20 +++ 20.11.2017 + AL 215.61 + CU 583.62
Your language: DE | EN
Discover the diversity of Faber Kabel.

Discover the diversity of Faber Kabel.

More cable is impossible.

Medium voltage cable NA2XS2Y 01X630/35 12/20 kV SW

Item number 012227

NA2XS2Y 01X630/35 12/20 kV SW
cable suitable for direct burial max. permitted temperature at conductor 90 °C min. installation temperature -20 °C installation in free air without UV-protection (cable UV-resistant) cable for use in water cable with VDE-certification

cable suitable for direct burial cable suitable for direct burial

max. permitted temperature at conductor 90 °C max. permitted temperature at conductor 90 °C

min. installation temperature -20 °C min. installation temperature -20 °C

installation in free air without UV-protection (cable UV-resistant) installation in free air without UV-protection (cable UV-resistant)

cable for use in water cable for use in water

cable with VDE-certification cable with VDE-certification

  • Datasheet
  • Application
  • Technical documents
StandardVDE 0276-620
Conductor materialaluminium
Conductor classclass 2 = stranded
InsulationXLPE DIX8
Sheathing materialpolyethylene DMP2
Colour outer sheathblack
Flame-retardantno
Maximum permitted conductor temperature90 °C
Permitted outer cable temperature, fixed70 °C
Permitted outer cable temperature, in motion/during installation-20 - +70 °C
Bending radius, fixed installation15 x DA
Nominal voltage Uo12000 V
Nominal voltage U20000 V
Maximum permitted operating voltage in three-phase systems24 kV
Test voltage42 kV
Conductor shape (Faber)RMv
Number of cores1
Conductor diameter32.5 mm
Nominal cross section630 mm²
Conductor resistance0.0469 Ohm/km
Insulation wall thickness5.5 mm
Ampacity in air (30 °C)890 A
Ampacity in ground (20 °C)675 A
Short-circuit current (1 s)59.2 kA
Wall thickness of sheath2.5 mm
Bending radius, fixed installation780 mm
Outer diameter approx.52 mm
Tensile strength (during installation)18900 N
colourblack

For installation in the ground, in water, outdoors, indoors and in cable ducts for power stations, industrial applications and distribution networks. It should be noted during installation in cable ducts and interior spaces that the PE-sheath is zero-halogen, yet not flame-retardant as defined under DIN VDE 0482-332-1. The high mechanical durability of the PE-sheath permits strong mechanical stress during installation or operation.

All images shown here are for illustrations and product reference purposes only.

Who we are.

Faber Kabel has numbered amongst the top providers in the cable and wire industry for over 47 years. We convince our customers with high-performing products and tested quality.

We are appreciated for our know-how, our service-orientation and our absolute adherence to delivery dates. Because we find: Nothing is more important than being a strong and dependable partner.

Contact.

Klaus Faber AG
Lebacher Straße 152 – 156
66113 Saarbrücken
Germany

Phone +49 681 97 11-0
Fax +49 681 97 11-289

Newsletter.