Item number 090265
flame retardant acc. IEC 60332-1-2
cable suitable for direct burial
max. permitted temperature at conductor 90 °C
min. installation temperature -5 °C
installation in free air without UV-protection (cable UV-resistant)
cable for use in water
cable with VDE-certification
cable conform to Low Voltage directive
Standard | VDE 0276-603 |
Conductor material | aluminium |
Insulation | XLPE DIX3 |
Sheathing material | PVC DMV6 |
Colour outer sheath | black |
Flame-retardant | VDE 0482-332-1-2/IEC 60332-1-2 |
UV-resistant | yes |
For outdoor use | yes |
Maximum permitted conductor temperature | 90 °C |
Permitted outer cable temperature, fixed | 90 °C |
Permitted outer cable temperature, in motion/during installation | -5 - +70 °C |
Bending radius, fixed installation | 15 x DA |
Nominal voltage Uo | 600 V |
Protective conductor | yes |
Nominal voltage U | 1000 V |
Maximum permitted operating voltage in three-phase systems | 1.2 kV |
Test voltage | 4 kV |
Core identification | colours acc. to VDE 0293 (HD308) |
Conductor shape (Faber) | SE |
Number of cores | 4 |
Nominal cross section | 150 mm² |
Conductor resistance | 0.206 Ohm/km |
Insulation wall thickness | 1.4 mm |
Ampacity in air (30 °C) | 311 A |
Ampacity in ground (20 °C) | 300 A |
Short-circuit current (1 s) | 14.1 kA |
Wall thickness of sheath | 2.4 mm |
Conductor class | class 1 = solid |
Outer diameter approx. | 42 mm |
Tensile strength (during installation) | 18002 N |
Cable shape | round |
colour | black |
For fixed installation indoors, outdoors, in the ground, in water and in conrete.