Sheathed building wire NYM-J 05X10 GR

Item number 020022

NYM-J 05X10 GR
flame retardant acc. IEC 60332-1-2 max. permitted temperature at conductor 70 °C min. installation temperature +5 °C cable with VDE-certification cable conform to Low Voltage directive

flame retardant acc. IEC 60332-1-2 flame retardant acc. IEC 60332-1-2

max. permitted temperature at conductor 70 °C max. permitted temperature at conductor 70 °C

min. installation temperature +5 °C min. installation temperature +5 °C

cable with VDE-certification cable with VDE-certification

cable conform to Low Voltage directive cable conform to Low Voltage directive

  • Datasheet
  • Application
  • Technical documents
StandardVDE 0250-204
Conductor materialbare copper
Conductor classclass 1, up from 16 sqmm class 2
InsulationPVC TI1
Sheathing materialPVC TM1
Colour outer sheathgrey RAL 7035
Flame-retardantVDE 0482-332-1-2/IEC 60332-1-2
Permitted outer cable temperature, fixed-40 - +70 °C
Permitted outer cable temperature, in motion/during installation5 - 70 °C
Nominal voltage Uo300 V
Protective conductoryes
Nominal voltage U500 V
Test voltage2 kV
Core identificationcolours acc. to VDE 0293 (HD 308); more than 5 cores: gn-ye + numbers
Conductor shaperound
Conductor shape (Faber)RE
Number of cores5
Nominal cross section10 mm²
Conductor resistance1.83 Ohm/km
Insulation wall thickness1 mm
Ampacity in air (30 °C)57 A
Wall thickness of sheath1.6 mm
Bending radius, fixed installation70.8 mm
Outer diameter approx.17.7 mm
colourgrey

For installation in, on or under plaster, in dry, damp or wet rooms as well as in walls and concrete (except for shaken, jolted, tamped concrete). Also suitable for installation outdoors if protected from sunlight.

All images shown here are for illustrations and product reference purposes only.

Who we are.

Faber Kabel has numbered amongst the top providers in the cable and wire industry for over 47 years. We convince our customers with high-performing products and tested quality.

We are appreciated for our know-how, our service-orientation and our absolute adherence to delivery dates. Because we find: Nothing is more important than being a strong and dependable partner.

Contact.

Klaus Faber AG
Lebacher Straße 152 – 156
66113 Saarbrücken
Germany

Phone +49 681 97 11-0
Fax +49 681 97 11-289

Newsletter.