Item number 050421
max. permitted temperature at conductor 90 °C
min. installation temperature -30 °C
installation in free air only with UV-protection (cable not UV-resistant)
cable conform to Low Voltage directive
harmonised cable/wire
Standard | EN 50525-2-21 |
Conductor material | copper, bare or tinned |
Conductor class | class 5 = fine stranded |
Insulation | rubber (EPR) EI4 |
Sheathing material | polyurethan |
Flame-retardant | no |
Maximum permitted conductor temperature | 90 °C |
Permitted outer cable temperature, fixed | -40 - +80 °C |
Nominal voltage Uo | 450 V |
Nominal voltage U | 750 V |
Core identification | colours acc. to VDE 0293 (HD308) |
Number of cores | 5 |
Nominal cross section | 70 mm² |
Conductor resistance | 0.272 Ohm/km |
Ampacity in air (30 °C) | 207 A |
Bending radius, fixed installation | 212 mm |
Bending radius, moving application | 636 mm |
Conductor class | class 5 = fine stranded |
Outer diameter approx. | 53 mm |
Colour of outer sheath | orange |
Tensile strength (during installation) | 5250 N |
Cable shape | round |
colour | orange |
In dry and wet environments as well as temporary outdoors under medium mechanical stress. For connection of electrical tools on building sites or in cold environments. The cable is highly oil-, abrasion- and impact resistant.
All images shown here are for illustrations and product reference purposes only.