Item number 036326
flame retardant acc. IEC 60332-3-24
flame retardant acc. IEC 60332-1-2
cable with low smoke IEC 61034
cable halogen-free
cable to a large extent oil resistant
max. permitted temperature at conductor 180 °C
installation in free air without UV-protection (cable UV-resistant)
Conductor material | tinned copper |
Conductor class | class 5 = fine stranded |
Insulation | silicone rubber |
Flame-retardant | VDE 0482-266-2-4/IEC 60332-3-24 (Cat. C) |
Smoke density | DIN EN 61034/IEC 61034 |
Halogen-free | DIN EN 50267/IEC 60754 |
UV-resistant | yes |
Oil-resistant | yes |
Maximum permitted conductor temperature | 180 °C |
Permitted outer cable temperature, fixed | -50 - +180 °C |
Bending radius, fixed installation | 6 x DA |
Nominal voltage Uo | 13800 V |
Nominal voltage U | 15000 V |
Test voltage | 31 kV |
Number of cores | 1 |
Nominal cross section | 16 mm² |
Ampacity in air (30 °C) | 153 A |
Conductor class | class 5 = fine stranded |
Outer diameter approx. | 15.8 mm |
Cable shape | round |
colour | black |
This connection cable is primarily used where great flexibility is required and a great thermal stress provided, e.g. transformers, generators, engines etc. For installation indoors and in cable ducts for power plant, industry and distribution networks. The halogen-free coating lends the cable good non-slip properties and abrasion-resistance as well as a very good resistance to transformer oil and light fuel oil.
All images shown here are for illustrations and product reference purposes only.