Including 1% procurement surcharge. No responsibility for the information!
+++ 23.11.2017 + AL 217.19 + CU 598.52 +++ 22.11.2017 + AL 215.65 + CU 595.88 +++ 21.11.2017 + AL 215.01 + CU 586.20 +++ 20.11.2017 + AL 215.61 + CU 583.62 +++ 17.11.2017 + AL 218.63 + CU 588.20
Your language: DE | EN
Discover the diversity of Faber Kabel.

Discover the diversity of Faber Kabel.

More cable is impossible.

Heat resistant cable 2GTL 01X10 13,8/15 kV SW

Item number 036264

2GTL 01X10 13,8/15 kV SW
flame retardant acc. IEC 60332-3-24 flame retardant acc. IEC 60332-1-2 cable with low smoke IEC 61034 cable halogen-free cable to a large extent oil resistant max. permitted temperature at conductor 180 °C installation in free air without UV-protection (cable UV-resistant)

flame retardant acc. IEC 60332-3-24 flame retardant acc. IEC 60332-3-24

flame retardant acc. IEC 60332-1-2 flame retardant acc. IEC 60332-1-2

cable with low smoke IEC 61034 cable with low smoke IEC 61034

cable halogen-free cable halogen-free

cable to a large extent oil resistant cable to a large extent oil resistant

max. permitted temperature at conductor 180 °C max. permitted temperature at conductor 180 °C

installation in free air without UV-protection (cable UV-resistant) installation in free air without UV-protection (cable UV-resistant)

  • Datasheet
  • Application
  • Technical documents
Conductor materialtinned copper
Conductor classclass 5 = fine stranded
Insulationsilicone rubber
Flame-retardantVDE 0482-266-2-4/IEC 60332-3-24 (Kat. C)
Smoke densityDIN EN 61034/IEC 61034
Halogen-freeDIN EN 50267/IEC 60754
UV-resistantyes
Maximum permitted conductor temperature180 °C
Permitted outer cable temperature, fixed-50 - +180 °C
Bending radius, fixed installation6 x DA
Nominal voltage Uo13800 V
Nominal voltage U15000 V
Test voltage31 kV
Nominal cross section10 mm²
Ampacity in air (30 °C)114 A
Outer diameter approx.14.9 mm
colourblack

This connection cable is primarily used where great flexibility is required and a great thermal stress provided, e.g. transformers, generators, engines etc. For installation indoors and in cable ducts for power plant, industry and distribution networks. The halogen-free coating lends the cable good non-slip properties and abrasion-resistance as well as a very good resistance to transformer oil and light fuel oil.

All images shown here are for illustrations and product reference purposes only.

Who we are.

Faber Kabel has numbered amongst the top providers in the cable and wire industry for over 47 years. We convince our customers with high-performing products and tested quality.

We are appreciated for our know-how, our service-orientation and our absolute adherence to delivery dates. Because we find: Nothing is more important than being a strong and dependable partner.

Contact.

Klaus Faber AG
Lebacher Straße 152 – 156
66113 Saarbrücken
Germany

Phone +49 681 97 11-0
Fax +49 681 97 11-289

Newsletter.